A modular controller is attractive because you can order the CPU and I/O functions separately. It also means the product list must reflect the electrical needs of the field instruments. Here is a practical order-of-operations for selecting NORVI X expansion modules.
1. Inventory each field signal
Create a table with the device name, direction (input or output), signal type, expected range, and normal/fault behavior. A proximity switch is not an analog transmitter; a 4–20 mA level sensor does not connect to a voltage-only analog input by default; and a relay output is not interchangeable with a transistor output.
2. Choose I/O families
- Digital status: DI4, DI8 or DI16 depending on point count and compatibility.
- AC signals: DA8, only when verified for the site’s line voltage and applicable certification.
- Relay outputs: R4 or R8 for appropriately rated loads.
- Solid-state outputs: Q4, Q8 or Q16 subject to output topology/current.
- Analog measurements: AV4 for appropriate voltage signals; AI4 for appropriate 4–20 mA loops.
- Temperature: RTD4 for verified RTD probes; TC4 for compatible thermocouples.
- Serial communication: UARTIO for supported RS-232/RS-485/UART expansion.
3. Validate bus addresses and direct GPIO
Many NORVI X modules share an I²C bus. Address conflicts can limit the number or mixture of otherwise compatible modules. Others use dedicated CPU GPIO lines. The X-DI4 and X-UARTIO are a known combination requiring particular caution because they use overlapping direct GPIO resources. Review the manufacturer’s current compatibility tables for the exact BOM.
4. Reserve engineering margin
Include spare I/O where justified, account for cabinet space and cable routes, validate supply power, and plan module replacements without changing the core wiring unnecessarily. Determine whether the chosen CPU’s local network is sufficient or whether the X3 LTE CPU is necessary.
5. Double-check model-specific open questions
As of the supplied U.S. price schedule, the exact signal type for X-T4 is inconsistent between the distributor sheet and manufacturer documentation, while X-MX4 and X-BKO have naming or I/O-count differences across sources. NORVI USA should verify these details before shipping a configuration. Do not substitute one variant for another based solely on similar marketing descriptions.
A useful BOM table
| Equipment | Signal | Count | Proposed module |
|---|---|---|---|
| Tank transmitters | 4–20 mA inputs | 4 | X-AI4 |
| Motor running contacts | Digital input | 8 | X-DI8 |
| Non-safety notifications | Relay output | 4 | X-R4 |
Send a comparable I/O list to NORVI USA and we can help match it to the catalog before you commit to an installation.